Title Advanced control of a water supply system: A case study
Author(s) Bakker, M.; Rajewicz, T.; Kien, H.; Vreeburg, J.H.G.; Rietveld, L.C.
Source Water Practice and Technology 9 (2014)2. - ISSN 1751-231X - p. 264 - 276.
DOI https://doi.org/10.2166/wpt.2014.030
Department(s) Environmental Technology
Publication type Refereed Article in a scientific journal
Publication year 2014
Keyword(s) Optimal control - Pressure management - Water demand forecasting
Abstract

Conventional automatic production flow control and pump pressure control of water supply systems are robust and simple: production flow is controlled based on the level in the clear water reservoir and pump pressure is controlled on a static set-point. Recently, more advanced computer-based control methods were developed in which production flow is controlled by using a short-term water demand forecasting model and pressure is controlled by a dynamic pressure control module. To assess the differences between conventional and advanced control, we examined operational data of water treatment plantGruszczyn that supplies drinking water to a part of the city of Poznan, Poland. We compared two periods of three weeks of conventional and advanced control. The comparison showed that with advanced control the variation in the production flow was 83% lower, and the pump pressure of the clear water pumps was 29% lower. The lower pressure resulted in 20% less background leakage and the overall system's energy costs were 11.5% lower.